Hitri kontakt

Firšt d.o.o.
+386 3898 35 00
+386 3898 35 35
info(at)first.si

Products - CONTROLLERS Room thermostats, Differential thermostats, Heating regulators, fittings, and accessories

ROTOTERM MR-B

for regulating domestic hot water in boiler or swimming pools

FIRŠT ROTOTERM MR-B is designed to regulate constanttemperature of domestic hot water in boiler or swimming pools.

  • Output for controlling motor actuator for mixing valves (series MV 120 EMV 110 S9000) and circulation pump.
  • Selector switch for choosing the operation (manual, auto), and to assis installer on start-up and technician during service.

Back to products / CONTROLLERS

ROTOTERM MR-B - for regulating domestic hot water in boiler or swimming pools

Code TYPE Description
21133 ROTOTERM MR-B (VF) Heating controller MR-B, 1 sensor, mounting kit
Control: 3-point (P)
Supply voltage: 230VAC, 50Hz
Power consumption: max.4VA
Output relay rating: 1(1)A, 230VAC, 50H
Temperature setting range: 0..90°C
Temperature measuring range:
-40°C..+160°C
Stationary area adjustment: 1..15°C
Reaction factor adjustment: 0,5..15
Circulation pump switching-off adjustment: 0..90°C
Sensors type: KTY 81-210
Kit weight: 0,5kg

Operation:

ROTOTERM MR-B is designed to regulate constant temperature of
domestic hot water in boiler or swimming pools. The controller is 3-point (PID) temperature controller of heating water.
The controller is built in microprocessor technology and meets the
latest quality standards. It offers a wide variety of programming options, allowing optimal controller settings for the selected object.

Code and electrical connection:

ROTOTERM-MR-B