Products - VALVES Rotary mixing, rotary diverting, ball valves, stainless steel ball valves ...

FDV 230

3-way diverting valve

The  FIRŠT FDV 231, 232 and 233 are compact diverting brass valves for use in small and medium sized heating and cooling installations. Valves are designed for switching between two heating circuits (diverting function) or two heating sources (changeover function). Valves are available in DN 15 – DN 32.

FIRŠT FDV 231, 232 and 233 are manual operated valves, designed for use in small and medium sized heating or cooling systems.

Three types of connections are available:

  • internal threads,
  • external threads,
  • compression fittings.

Back to products / VALVES

FDV230

FDV 231, internal threads

CODE TYPE DN Kvs Connection A B C   Weight (kg)
41104 FDV 231 DN15 Rp ½" FFF 15 3 Rp ½" 36 72 45   0,41
41105 FDV 231 DN20 Rp ¾" FFF 20 7 Rp ¾" 36 72 45   0,47
41106 FDV 231 DN25 Rp 1" FFF 25 11 Rp 1" 41 82 45   0,51
41107 FDV 231 DN32 Rp 1¼" FFF 32 15 Rp 1¼" 47 94 48   0,84


FDV 232, external threads

CODE TYPE DN Kvs Connection A B C   Weight (kg)
41128 FDV 232 DN15 G ¾" MMM 15 3 G ¾" 36 72 45   0,39
41128 FDV 232 DN20 G 1" MMM 20 7 G 1" 36 72 45   0,43
41130 FDV 232 DN25 G 1¼" MMM 25 11 G 1¼" 41 82 45   0,58
41131* FDV 232 DN32 G 1½" MMM 32 15 G 1½" 47 94 48   0,80


FDV 233, compression fittings

CODE TYPE DN Kvs Connection A B C   Weight (kg)
41136 FDV 233 DN20 C22mm CCC 20 7 CPF 22 mm 36 72 45   0,48
41137 FDV 233 DN25 C28mm CCC 25 11 CPF 28 mm 41 82 45   0,61
* Valves are available on special request.
Pressure class: PN 10
Medium: water, glycol < 50%
Media temperature: min. -10°C, max. +110°C
Leakage (Δ p=1 bar): max. 0,2% Kvs
Max. diff. pressure: 1 bar
Connections: Rp internal thread (EN 10226-1)
G external thread (ISO 228-1)
compression fittings (EN 1254-2)

Material:

Valve body: Brass, CW617N          
Shaft and rotor: Brass, CW617N
Bushing: PTFE
O-Rings: EPDM,FKM

PED 97/ 23/ EC art 3.3

Operation:

FDV230

Application examples:

Diverting to two heat users (radiator or water heater), or changeover between two heat sources (oil boiler or solid fuel boiler).

FDV230_03



ROTODIVERT-M
ROTODIVERT-M
UNI-D2P
UNI D2P

ROTODIVERT-M
UNI D2P