EUROMIX-H is an electric motor actuator designed for operating rotary mixing valves. Actuators are controlled by 3-point signal. The actuator can be manually operated.
Valves are available in DN 25, with by-pass and pump connection and are rated PN10.
FIRŠT FMV H-151 valves have the running nut for pump connection, the male connection to the manifold and the adjustable bypass on the way back and adjustable parallel dimension (125-90mm), with T pieces.
Valves are intended to be installed in heatind and/or cooling systems, sanitary applications and distribution groups. Valves have equal percentage flow characteristic.
CODE | TYPE | DN | Kvs | Voltage | Rolation time | Connection | A | B | C | D | Weight (kg) |
11076 | EUROMIX-H 151 | 25 | 10 | 230V~50Hz | 105s/90° | G 1½", G1" M, Rp 1½" | 58 | 90 | 37 | 116 | 1,2 |
11077 | EUROMIX-H 151 | 25 | 6 | 230V~50Hz | 105s/90° | G 1½", G1" M, Rp 1½" | 58 | 90 | 37 | 116 | 1,2 |
CODE | TYPE | DN | Kvs | Voltage | Rolation time | Connection | A | B | C | D | E | Weight (kg) |
11092 | EUROMIX-H 151 | 25 | 10 | 230V~50Hz | 105s/90° | G 1½", G1" M, Rp 1½" | 58 | 90 | 37 | 116 | 125-90 | 1,7 |
11093 | EUROMIX-H 151 | 25 | 6 | 230V~50Hz | 105s/90° | G 1½", G1" M, Rp 1½" | 58 | 90 | 37 | 116 | 125-90 | 1,7 |
Pressure class: | PN 10 |
Medium: |
water, glycol < 50%
water quality as per VDI 2035 |
Media temperature: | min. +2°C, max. +110°C |
Leakage (Δ p=1 bar): | max. 0,1% Kvs |
Max. diff. pressure: | 1 bar |
Connections: |
Rp internal thread (EN 10226-1) G external thread (ISO 228-1) |
Valve body: | Brass, CW617N |
Shaft and rotor: | Brass, CW617N |
Bushing: | PTFE |
O-Rings: | EPDM,FKM |
Control: | 3-point SPDT |
Supply voltage: | 230V~50Hz |
Rotation time: | 105s/90° |
Power consumption: | 3,5 VA |
Max.Torque: | 8 Nm |
Protection class: |
II
|
Enclosure rating: | IP44 |
Connection cable: | 3 x 0,5 mm2 , l= 2m |
Direction of rotation: | defined |
Manual control: | knob on actuator cover |
Position indicator: | mechanical, on the actuator cover |
Ambient temperature: | 0°C..+55°C |
Storage temperature: | -10°C..+70°C |
Humidity: | 0%..80% R.h. (non condensed) |
EQUAL PERCENTAGE FLOW CHARACTERISTIC
Valves allow mixing between two fluids, warm and cold water, to get the desired temperature. The valve is right mounting with adjustable bypass. The bypass can be adjusted up to 50% of the total valve flow.