Hitri kontakt

Firšt d.o.o.
+386 3898 35 00
+386 3898 35 35
info(at)first.si

Products - UNITS Rotary units, Zone units, Ball valves, Programmable motorized ball valves

S9000 220C-M

2-way zone units with Clip system

The FIRŠT FBV 220C-M control valves are compact 2-ways motorised brass ball valves with characterizing inserts. Insert assures excellent control characteristics with equal percentage flow characteristics which perceftly matches the heat output characteristics of heating units.

Control valves are available in DN 15 – DN 25, with internal or external thread, union fittings and compression fittings.

FIRŠT control valves with electric actuators are used as control elements for HVAC applications (for use in heating systems, solar systems, zone heating etc.). Equal percentage flow characteristics produces excellent control characteristics and linear thermal output according to the valve opening angle.

Five types of connections are avaliable: internal threads (FBV 220CM), external threads and union fitting (FBV 221C-M), union fit. (FBV 222C-M), compression fittings (FBV 223C-M), external threads (FBV 224C-M).


Back to products / UNITS

S9000-200C-M

FBV 220C-M, internal threads

CODE TYPE DN Kvs Voltage Rolation time Control Connection A B C Weight (kg)
14375 S9FR7-K 220C-M DN15 Rp ½" FF 15 4 24V~50Hz 110s/90° 0...10V Rp ½" 62
104 0,24
14376 S9FR7-K 220C-M DN20 Rp ¾" FF 20 7,5 24V~50Hz 110s/90° 0...10V Rp  ¾" 68
107 0,35
14377 S9FR7-K 220C-M DN25 Rp 1″ FF 25 13 24V~50Hz 110s/90° 0...10V Rp 1″ 81
112 0,55


FBV 221C-M, external threads and union fitting

CODE TYPE DN Kvs Voltage Rolation time Control Connection A B C Weight (kg)
14379 S9FR7-K 221C-M DN15 Rp/R ½" FU 15 4 24V~50Hz 110s/90° 0...10V Rp/R ½" 62 90
104 0,30
14380 S9FR7-K 221C-M DN20 Rp/R ¾" FU 20 7,5 24V~50Hz 110s/90° 0...10V Rp/R  ¾" 68 102
107 0,40
14381 S9FR7-K 221C-M DN25 Rp/R 1″ FU 25 13 24V~50Hz 110s/90° 0...10V Rp/R 1″ 81 114
112 0,70


FBV 222C-M, union fittings

CODE TYPE DN Kvs Voltage Rolation time Control Connection A B C Weight (kg)
14383 S9FR7-K 222C-M DN15 R ½" UU 15 4 24V~50Hz 110s/90° 0...10V R ½" 62 119
104 0,37
14384 S9FR7-K 222C-M DN20 R ¾" UU 20 7,5 24V~50Hz 110s/90° 0...10V R  ¾" 74 136
107 0,55
14385 S9FR7-K 222C-M DN25 R 1″ UU 25 13 24V~50Hz 110s/90° 0...10V  R 1″ 82 149
112 0,86


FBV 223C-M, compression fittings

CODE TYPE DN Kvs Voltage Rolation time Control Connection A B C Weight (kg)
14387 S9FR7-K 223C-M DN15 D15 CC 15 4 24V~50Hz 110s/90° 0...10V CPF 15mm 62
104 0,27
14388 S9FR7-K 223C-M DN20 D22 CC 20 7,5 24V~50Hz 110s/90° 0...10V CPF 22mm 72
107 0,41
14389 S9FR7-K 223C-M DN25 D28 CC 25 13 24V~50Hz 110s/90° 0...10V CPF 28mm 82
112 0,62


FBV 224C-M, external threads

CODE TYPE DN Kvs Voltage Rolation time Control Connection A B C Weight (kg)
14390 S9FR7-K 224C-M DN15 G ¾"  MM 15 4 24V~50Hz 110s/90° 0...10V G ¾" 62
104 0,25
14391 S9FR7-K 224C-M DN20 G 1" MM 20 7,5 24V~50Hz 110s/90° 0...10V G 1″ 74
107 0,38
14392 S9FR7-K 224C-M DN25 G 1¼" MM 25 13 24V~50Hz 110s/90° 0...10V G 1¼" 82
112 0,60

VALVES

Nominal pressure: PN 32 (for general applications)
Medium: drinking water, water, glycol < 50%, non aggressive liquids
water quality as per VDI 2035
Media temperature: min. +2°C, max. +110°C
Max. diff. pressure: 3 bar (recommended max. diff. pressure
for low noise operation: 2 bar)
Connections: Rp internal thread (EN 10226-1)
R external thread (EN 10226-1)
G external thread (ISO 228-1)
compression fittings (EN 1254-2)

Material

Valve body: Brass, CW617N
Ball: Brass, CW617N
Seals: PTFE, EPDM Perox, FPM

ACTUATOR

Control: 0...10 VDC, 4..20 mA
Output signal:: 0... 10 VDC, max < 0,5 mA/ 10V
Supply voltage: 24 VAC 50Hz
Rotation time: 110s/90°
Power consumption: 3,5 VA (operation), 1,5 VA (stand by)
Max.Torque: 5 Nm
Protection class: II
Enclosure rating: IP44
Connection cable: 1 m, 4 x 0,5 mm2
Direction of rotation: defined CW/CCW
Manual control: with handle and button on the cover
Position indicator: handle with reversible scale
Ambient temperature:   0°C..+55°C
Storage temperature: -10°C..+70°C
Humidity: 0%..80% R.h. (non condensed)

Operation:

Actuator can be installed only in one position.                                  EQUAL PERCENTAGE FLOW CHARACTERISTIC

S9000-200C-M

Electrical connection:

                                                                                            Actuators have DIP switches for setting different functions of actuators.

S9000-200C-M

Installation examples:

S9000-200C-M

Features and options

■ Auxiliary switch: one potential free auxiliary switch in the end position of the actuator is available as an option.
■ Manual control: with or without manual control handle.
■ Solar/cooling adapter: Heat barrier for protection of the actuator in solar or cooling systems.
■ Molex connector: optional Molex connector (IP40 and optional specially sealed Molex cable (IP44).
■ Different rotating times: 20s/90, 40s/90°, 80s/90°, 110s/90°