The FIRŠT FDV 231C, 232C and 233C are compact diverting brass valves for use in small and medium sized heating and cooling installations. Valves are designed for switching between two heating circuits (diverting function) or two heating sources (changeover function). Valves FDV 230C are available in DN 15 – DN 32.
FIRŠT FDV 231C, 232C and 233C are manual operated valves designed for use in small and medium sized heating or cooling systems.
Three types of connections are available:
CODE | TYPE | DN | Kvs | Connection | A | B | C | Weight (kg) | |
41124 | FDV 231C DN15 Rp ½" FFF | 15 | 3 | Rp ½" | 36 | 72 | 57 | 0,47 | |
41125 |
FDV 231C DN20 Rp ¾"
FFF |
20 | 7 | Rp ¾" | 36 | 72 | 57 | 0,54 | |
41126 |
FDV 231C DN25 Rp 1"
FFF |
25 | 11 | Rp 1" | 41 | 82 | 57 | 0,57 | |
41127* | FDV 231C DN32 Rp 1 ¼" FFF | 32 | 15 | Rp 1 ¼" | 47 | 94 | 60 | 0,89 | |
41144* |
FDV 231C DN40 Rp 1 ½"
FFF |
40 | 25 | Rp 1 ½" | 53 | 106 | 65 | 1,20 | |
41145* |
FDV 231C DN50 Rp 2"
FFF |
50 | 40 | Rp 2" | 60 | 120 | 66 | 1,78 |
CODE | TYPE | DN | Kvs | Connection | A | B | C | Weight (kg) | |
41132 | FDV 232C DN15 G ¾" MMM | 15 | 3 | G ¾" | 36 | 72 | 57 | 0,45 | |
41133 | FDV 232C DN20 G 1" MMM | 20 | 7 | G 1" | 36 | 72 | 57 | 0,59 | |
41134
|
FDV 232C DN25 G 1 ¼" MMM | 25 | 11 | G 1 ¼" | 41 | 82 | 57 | 0,64 | |
41135* |
FDV 232C DN32 G 1 ½"
MMM |
32 | 15 | G 1 ½" | 47 | 94 | 60 | 0,85 |
CODE | TYPE | DN | Kvs | Connection | A | B | C | Weight (kg) | |
41138 | FDV 233C DN20 C22mm CCC | 20 | 7 | CPF 22 mm | 36 | 72 | 57 | 0,55 | |
41139 | FDV 233C DN25 C28mm CCC | 25 | 11 | CPF 28 mm | 41 | 82 | 57 | 0,66 |
Pressure class: | PN 10 |
Medium: | water, glycol < 50% |
Media temperature: | min. -10°C, max. +110°C |
Leakage (Δ p=1 bar): | max. 0,2% Kvs |
Max. diff. pressure: | 1 bar |
Connections: |
Rp internal thread (EN 10226-1)
G external thread (ISO 228-1) compression fittings (EN 1254-2) |
Valve body: | Brass, CW617N |
Shaft and rotor: | Brass, CW617N |
Bushing: | PTFE |
O-Rings: |
EPDM,FKM |
Diverting to two heat users ( radiator or water heater), or changeover between two heat sources (oil boiler or solid fuel boiler)
![]() S9000 2P-ND-DIV |
![]() UNI D2P |
|
■
S9000 2P-ND-DIV ■ UNI D2P |